Power Conditioning Equipment

POWER CONDITIONING EQUIPMENT

  • Power conditioner is a combination of Voltage stabilizer and Transformer housed in a common enclosure.The purpose of this equipment shall be suitable for providing stabilized voltage within +/-1%.
  • Magnetic and Controls has the capability to design and manufacture the power conditioning equipment with different input voltage ranges with different output voltages.
  • We can manufacture the power conditioning equipment with specially designed Delta Star and Delta Zig Zag transformers

OUR POWER CONDITIONING EQUIPMENT INCLUDE

  • SERVO STABILIZER
  • SPECIALLY DESIGNED DELTA ZIG ZAG  K-RATED ISOLATION TRANSFORMER
  • MICROPROCESSOR BASED CONTROL SYSTEM FOR MEASUREMENT AND CORRECTION
  • MIN AND MAX VOLTAGE/CURRENT DISPLAY
  • DIGITAL METER HAVING PARAMETERS MEASURED LIKE VOLTAGE ,CURRENT AND FREQUENCY
  • LOW AND HIGH VOLTAGE CUT OFF
  • TRUE RMS METER
  • PHASE SEQUENCE CORRECTOR
  • The Zig Zag transformers contains six coils on three cores.The first coil on each core is connected contrariwise to the second coil on the next core
  • Zig Zag transformers has two windings on each leg
  • Each leg of the Zig Zag connection is connected to a winding from another which is out of phase
  • Zig Zag winding of the transformer limits the circulation of harmonics(3rd,6th,9th)
  • Zig Zag connections of transformers is also known as interconnected star connection
  • This connection has some of the feature of the star and Delta connection
  • Zig Zag transformers offers a low impedance path to Zero sequence components under the fault condition so it is used as earthing transformer also
  • Harmonic voltages presented in the system to some extent can be cancelled in Zig Zag winding due to opposite connection of Zig Zag winding
  • Delta Star transformer do not eliminate harmonics.K rated Isolation transformers can be designed to withstand harmonics and are designed to tolerate the heating effects of harmonics created by electronic equipment
  •  These Delta Zig Zag transformers are also known as “HARMONIC MITIGATING TRANSFORMER” which also mitigates the triplen harmonics
  •  Zig Zag secondary  winding in transformers causes phase shift in triplen harmonics which results in cancelling effects
  •  Unlike Delta star transformer the Delta Zig Zag transformer actually treat the triplen harmonics in the Zig Zag winding
  •  We manufacture Zig Zag transformers with Class H insulation and are designed to eliminate the “Skin effect”
  •  Zig Zag winding traps the triplen harmonics current and prevents them from travelling upstream where they can produce undesirable effects
  •  The Zig Zag transformer has no phase displacement between primary and secondary winding.Therefore the Delta Zig Zag transformer can be used in the same manner as Delta Delta or Star Star transformer without any phase shift
VOLTAGE STABILIZER TYPE SCVS WITH 3 PH INPUT & 3 PH OUTPUT FOR UNBALANCED LOAD AND UNBALANCED INPUT CONDITION WITH INDEPENDENT VOLTAGE SENSING AND REGULATION
RATING 10 KVA SCVS TO 300 KVA SCVS
INPUT VOLTAGE RANGE 340-480/360-460 V,3 PH 4 WIRE

360-480/295-470 V,3 PH 4 WIRE OR ANY CUSTOM BUILT AS PER CUSTOMER REQUEST

OUTPUT VOLTAGE RANGE 400/415/380/220 or any custom built voltage
FREQUENCY RANGE 50/60 HZ
SERVO CONTROL TYPE MICRO CONTROL BASED TRUE RMS SENSING
SERVO MOTOR DRIVE TRIAC BASED AC SYNCHRONOUS MOTOR
AVG CORRECTION SPEED >30 V /SEC(LINE TO NEUTRAL)
PROTECTION UNDER AND OVER VOLTAGE CUT OFF WITH TIME DELAY
INPUT BREAKER AND OUTPUT BYPASS
OTHER PROTECTIONS PHASE PREVENTION/PHASE REVERSAL INDICATION
OUTPUT CONTACTOR
OUTPUT BYPASS/OUTPUT MCCB
EMERGENCY POWER OFF
PARAMETERS DISPLAYED FAULT ANNUNCIATION,100 EVENT LOG WITH TIME AND DATE
INPUT AND OUTPUT METER MFM METER WITH COMMUNICATION PORT
DIMMER HIGH QUALITY DIMMER WITH MOTOR CONTROL
BBT Cu or Al BASED ON CUSTOMER REQUIREMENT
ENCLOSURE AS PER CUSTOMER REQUIREMENTS
ITEM K-RATED ISOLATION TRANSFORMER
RATING 10 KVA TO 300 KVA ITR
INPUT VOLTAGE 380/400/415 OR ANY CUSTOM DESIGN
OUTPUT VOLTAGE 380/400/415 OR ANY CUSTOM DESIGN
STANDARDS FOLLOWED AS PER IEC 60076 OR IS 2026
CORE CRGO
WINDING MATERIALS Cu/Al
CAPACITY RATING AS PER CUSTOMER REQUIREMENT
CONFIGURATION DELTA ZIG ZAG OR ANY OTHER VECTOR GROUP AS PER CUSTOMER REQUIREMENT
K-RATING K1/K4/K13/K20 WITH BUILT IN DERATING AS PER UL 1561
FREQUENCY TOLERANCE +5%,-5%
PRODUCT CERTIFICATIONS CE CERTIFIED
CABLE ENTRY BASED ON CUSTOMER REQUIREMENT

We Also Automatic Phase sequence at the input side with 125% over load capacity.

In this case during the event of Phase reversal system will change the phase sequence

Automatically without any manual operation